Wire Size & Voltage Drop Calculator (NEC and IEC) avatar

Wire Size & Voltage Drop Calculator (NEC and IEC)

Pricing

Pay per event

Go to Apify Store
Wire Size & Voltage Drop Calculator (NEC and IEC)

Wire Size & Voltage Drop Calculator (NEC and IEC)

Wire and cable sizing for electrical circuits: NEC ampacity (AWG, kcmil) or IEC 60364 (mm²) with derating, breaker, voltage drop, ground wire and fault current. Text or JSON in. For AI agents.

Pricing

Pay per event

Rating

0.0

(0)

Developer

Jumble Mog

Jumble Mog

Maintained by Community

Actor stats

0

Bookmarked

2

Total users

1

Monthly active users

5 hours ago

Last modified

Features

Limited permissions

Share

Size the wire for any circuit from one line of text. Type 30 A continuous, 240 V single phase, 150 ft, copper THHN or 11 kW, 400 V three phase, 80 m, XLPE. You get back:

  • The wire size: the smallest conductor that carries the current, is protected by a standard breaker, and keeps the voltage drop within your limit (3% unless you say otherwise).
  • The voltage drop in volts and percent, the voltage at the load, the losses, and the longest run that size allows.
  • The breaker and the grounding conductor, upsized in proportion when the wire was upsized for voltage drop.
  • Which limit decided: ampacity or voltage drop, and the sizes each one alone would need.
  • A chart of voltage drop and ampacity for the sizes around the pick.

Two rule sets:

  • NEC (US): AWG and kcmil, Table 310.16 at 60, 75 or 90 °C. It applies ambient and bundling factors, the terminal temperature limit, the small-conductor breaker limits and the next-size-up rule. Continuous loads are taken at 125%, and motors get their current from Tables 430.248 and 430.250.
  • IEC 60364-5-52 (UK, EU and most of the world): mm² for PVC or XLPE cable, in conduit (method B1) or clipped to a wall (method C). It applies ambient and grouping factors, and the breaker meets Ib ≤ In ≤ Iz.

It also:

  • Checks a size you name: check 4 AWG tells you whether it works and why not.
  • Finds the fault current at the load from the source's fault level or a transformer's kVA and impedance.
  • Turns loads into amps: kW with power factor, kVA, or motor horsepower.

It's made for:

  • Electricians, electrical engineers and contractors doing quick checks and takeoffs.
  • Solar and EV-charger installers, and DC runs for RVs, boats and off-grid systems.
  • Facility managers and students.
  • AI agents that need a real wire size instead of a guess.

A 30 A continuous circuit at 240 V over 150 ft sized by this Actor: 8 AWG copper on a 40 A breaker with a 2.51% voltage drop, shown against 12, 10, 6 and 4 AWG for voltage drop and ampacity

How to use it

  1. Write Circuits, one per line, such as 40 A, 120 V, 200 ft, copper. The form has examples.
  2. Optionally set the Code, a Default voltage, a Default conductor or a Default voltage-drop limit.
  3. Click Start. Each circuit is a row in the results, with its summary, chart and report.

Writing circuits

A line can hold any of these, in any order:

  • The load: 30 A, 10 kW, 15 kVA, 20 hp motor, plus continuous and pf 0.85.
  • The supply: 240 V, single phase, three phase or DC.
  • The length: one way, such as 150 ft or 45 m.
  • The conductor:
    • The metal: copper or aluminum.
    • The insulation: THHN, THWN, XHHW-2, TW, NM-B, UF, PVC or XLPE.
    • Or a rating, such as 75 C rated.
  • Conditions:
    • 40 C ambient.
    • Grouping: 6 current-carrying conductors (NEC) or 3 circuits grouped (IEC).
    • method C.
    • 2 parallel sets.
  • Limits and checks: 2% drop, check 4 AWG or check 6 mm2, and a source fault level such as 65 kA.

Objects work too, with the same fields named; see Input.

The code is picked from what you write: feet, AWG and 120/208/240/277/480 V mean the NEC; meters, mm² and 230/400 V mean IEC. You can also set it.

Examples

All of these ran on this Actor; the numbers are from the results.

CircuitResult
30 A continuous, 240 V single phase, 150 ft, copper THHN8 AWG on a 40 A breaker (37.5 A design current; 10 AWG carries only 35 A at 75 °C), 2.51% drop
40 A, 120 V, 200 ft, copper3 AWG for voltage drop (8 AWG carries the current but drops 9.42%), 2.86% drop, 4 AWG ground wire upsized by 250.122(B)
20 hp motor, 480 V three phase, 300 ft, copper THWN27 A from Table 430.250, 10 AWG, 2.97% drop
100 A, 480 V 3 phase, 500 ft, aluminum XHHW-2, 6 current-carrying conductors, 40 C ambient, check 4 AWG3/0 AWG aluminum (128 A after 0.91 and 0.8 factors), 2.38% drop. The 4 AWG asked about fails on both counts
11 kW, 400 V three phase, 80 m, XLPE, pf 0.85, 3 circuits grouped18.7 A: 4 mm² (25.9 A after grouping) on a 20 A breaker, 2.86% drop
200 A at 208 V three phase, 250 ft, copper THHN, from a 150 kVA 4% transformer250 kcmil for voltage drop, 2.71%. Fault current 10.4 kA at the transformer, 4.57 kA at the load

The tests check that:

  • Areas match ASTM B258.
  • Resistance matches NEC Chapter 9 Table 8 (12 AWG: 1.98 Ω/kft at 75 °C).
  • Correction factors match Table 310.15(B)(1) and IEC Table B.52.14.
  • The 75 °C terminal rule, the 240.4(D) small-conductor limits and the next-size-up rule are applied.
  • Voltage drop matches the hand formula, for AC and DC.
  • Motor currents match the tables, and IEC sizes match the tables.

How-to examples

Each example is a complete input; the results are from runs of the Actor (also listed under Examples).

How to find what size wire you need for a circuit (NEC)

{"circuits": ["30 A continuous, 240 V single phase, 150 ft, copper THHN"]}

Result: 8 AWG on a 40 A breaker. The design current is 37.5 A, and 10 AWG carries only 35 A at 75 °C. The voltage drop is 2.51%.

How to calculate voltage drop on a long run

{"circuits": ["40 A, 120 V, 200 ft, copper"]}

Result: 3 AWG for voltage drop, at 2.86%. 8 AWG carries the current but drops 9.42%. The ground wire is upsized to 4 AWG by NEC 250.122(B).

How to size a cable in mm² (IEC 60364)

{"circuits": ["11 kW, 400 V three phase, 80 m, XLPE, pf 0.85, 3 circuits grouped"]}

Result: 18.7 A, so 4 mm² (25.9 A after grouping) on a 20 A breaker, with a 2.86% drop. Motors work from horsepower too: 20 hp motor, 480 V three phase, 300 ft, copper THWN gives 27 A from Table 430.250 and 10 AWG.

How to let an AI agent size wires

Add this Actor to the Apify MCP server with https://mcp.apify.com/?tools=jumblemog/wire-size-calculator. The agent passes the circuit as one line and answers with the size, the breaker and the voltage drop from the code tables, instead of a rule of thumb.

FAQ

Which codes does it follow? The NEC (US) with Table 310.16, and IEC 60364-5-52 for mm² cables in the UK, EU and most of the world. The code is picked from the units you use, or set code.

Does it apply derating? Yes: ambient temperature and bundling or grouping factors, the 75 °C terminal rule, the small-conductor breaker limits and the next-size-up rule.

Can it check a wire size I already have? Yes. Add check 4 AWG and it says whether that size passes and why not.

Does it do aluminum and DC? Yes, copper or aluminum, AC single or three phase, and DC.

Is it a substitute for an electrician? No. It's a calculation to plan and check against; local codes and an inspector have the final word.

Input

FieldWhat it is
circuitsCircuits, as text lines or objects.
codeauto, NEC or IEC.
voltage, material, maxVoltageDropDefaults for circuits that don't give them.
chartsDraw charts (default on).

A circuit as an object takes:

  • Load: current, or load ("10 kW", "15 kVA", "20 hp"); powerFactor; continuous; motor.
  • Supply: voltage and phase (1, 3 or dc).
  • Run: length (one way); parallelSets; reactance (Ω/km or Ω/kft); cable (multicore, for a lower reactance).
  • Conductor: material; insulation or temperatureRating; terminalRating (NEC, default 75 °C).
  • Conditions: method (IEC: B1 or C); ambient; conductorsInRaceway (NEC) or circuitsGrouped (IEC).
  • Limits and checks: maxVoltageDrop; size (to check one).
  • Source: faultCurrent, or transformer ({"kVA": 150, "impedance": "4%"}).
  • Other: code, title, and text (a line to start from, which the other fields override).

Output

One dataset item per circuit, also saved together in the run's OUTPUT record:

{
"request": 1, "status": "ok", "code": "NEC",
"title": "8 AWG copper for 30 A at 240 V",
"summary": "30 A continuous load at 240 V single phase over 150 ft: 8 AWG copper carries 50 A on a 40 A breaker, voltage drop 2.51% (6.01 V).",
"circuit": {"voltage": 240, "system": "single phase", "loadCurrent": 30, "designCurrent": 37.5, "length": 150,
"material": "Copper", "insulationRating": 90, "terminalRating": 75, "maxVoltageDropPercent": 3},
"recommended": {"size": "8 AWG", "areaMm2": 8.366, "ampacity": 50, "breaker": 40, "voltageDrop": 6.01,
"voltageDropPercent": 2.51, "receivingVoltage": 233.99, "conductorTemperature": 51.6, "loss": 194.5},
"limitedBy": "ampacity", "sizeForAmpacity": "8 AWG", "sizeForVoltageDrop": "8 AWG",
"maxLengthAtRecommended": 179.6,
"groundingConductor": {"size": "10 AWG", "rule": "NEC Table 250.122"},
"sizes": [{"size": "14 AWG", "ampacity": 20, "breaker": 40, "meetsAmpacity": false, "voltageDropPercent": 13.72, "...": "..."}, "..."],
"imageUrl": "https://api.apify.com/v2/key-value-stores/.../records/001-....png"
}

checked has the size asked about, and faultCurrent has the fault current at the source and at the load, in amps. Lengths are in feet for the NEC and meters for IEC (see unitLabels). A circuit that can't be sized has "status": "failed" and the reason in error, and isn't billed.

How it works

  1. Reading the circuit: the line is split into its parts. Loads become amps:
    • kW use the power factor;
    • kVA use the voltage;
    • horsepower uses the NEC motor tables.
  2. Ampacity of each standard size:
    • NEC: the table value at the insulation's temperature column, times the ambient factor and the bundling factor. The result is held to the terminal column.
    • IEC: the Annex B value for the method and the number of loaded conductors, times the ambient factor and the grouping factor.
  3. The breaker for each size: the smallest standard rating at or above the design current, checked against the conductor's ampacity.
  4. Voltage drop for each size:
    • The formula is k·I·L·(R cos φ + X sin φ), with k = 2 for single phase and DC and √3 for three phase.
    • R is taken at the conductor's estimated operating temperature, from its area and the metal's resistivity.
    • X defaults to 0.15 Ω/km for single conductors in a raceway and 0.08 Ω/km for multicore cable.
  5. The pick is the smallest size that passes both checks.
  6. Charts are drawn with Vega-Lite and rendered with vl-convert.

Pricing

You pay one low price per circuit, at the price shown on this page. It includes the chart and the report. Circuits that can't be sized are never charged. If you set a maximum cost per run, the Actor stops before a circuit that wouldn't fit.

Speed

Each circuit takes a few milliseconds plus its chart. A run through the API answers in about 5 to 10 seconds, including the cloud container starting.

Tips and limits

  • Check your local code and the equipment's instructions. This tool applies the main sizing rules; an inspector applies all of them.
  • Not included: conduit fill; the NEC's own Table 9 impedances (resistance is computed from the metal instead, which matches Table 8 within about 2%); and the IEC methods other than B1 and C.
  • IEC aluminum capacities are taken as 78% of copper's, typical of the IEC tables. IEC aluminum sizes start at 16 mm².
  • Motors: conductors are sized at 125% of the table current. Size the short-circuit protection by NEC 430.52 and the overload protection from the nameplate.
  • Fault current: a bolted fault with the conductors at 20 °C. The source X/R is taken as 4.
  • Limits: 500 circuits per run, 1 to 20 parallel sets.

For AI agents and developers

This Actor works with the Apify MCP server, so AI agents can call it as a tool. Pass circuits as plain text and read summary, recommended.size, recommended.breaker and recommended.voltageDropPercent. A direct API call that waits for the answer:

curl -X POST "https://api.apify.com/v2/acts/jumblemog~wire-size-calculator/run-sync-get-dataset-items?token=YOUR_TOKEN" \
-H "Content-Type: application/json" \
-d '{"circuits": ["48 A continuous EV charger, 240 V single phase, 90 ft, copper THHN"]}'

run-sync instead returns the run's OUTPUT: the status, the counts and every result as JSON.

In Python, with the apify-client package:

from apify_client import ApifyClient
client = ApifyClient("YOUR_TOKEN")
run = client.actor("jumblemog/wire-size-calculator").call(run_input={
"circuits": [{"load": "7.4 kW", "voltage": "230 V", "phase": 1, "length": "35 m", "insulation": "PVC",
"method": "C", "maxVoltageDrop": "5%"}],
})
for item in client.dataset(run["defaultDatasetId"]).iterate_items():
print(item["summary"])

Credits

  • Charts: Vega-Lite and vl-convert (BSD-3-Clause), with the Inter font (SIL Open Font License).
  • Rules and tables:
    • NFPA 70, National Electrical Code: Tables 310.16, 310.15(B)(1) and (C)(1), 240.4(D), 240.6(A), 250.122, 430.248 and 430.250, and Chapter 9 Table 8.
    • IEC 60364-5-52, Selection and erection of electrical equipment: Wiring systems, Annex B.
    • IEC 60364-5-54, Table 54.2.
    • ASTM B258, Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes.